Cooling

How AI campuses remove heat · From the chip to the outdoors · One flagship per regime

AI racks now draw more power than air can carry away, so cooling has moved from fans to water loops bolted to the chips. Each page here follows one step of the heat path, from cold plates at Microsoft's Fairwater to the wastewater plant SpaceXSI plans for Colossus in Memphis.

Cooling regimes by rack power on a log scale: air to about 50 kW, rear-door heat exchangers to about 50 kW, air-assisted liquid to about 140 kW, direct-to-chip from about 100 to 600 kW and immersion claims to several hundred kW; and the heat path from chip to outdoors WHICH COOLING FITS WHICH RACK, KW (LOG) 5 10 50 100 500 1,000 Air, outside air Rear-door coils Air-assisted liquid Direct-to-chip Immersion GB200 THE HEAT PATH CHIP~1-2 kW each COLD PLATE45°C in, 65 out CDUHeat exchanger FACILITYClosed or open REJECTIONTowers or dry Heat can also be sold: see Heat Reuse on the Energy pages. Water used at power plants is about 12 times the water used on site (2023).
Air limit
~40-50 kW/rack
GB200 rack
~132 kW
Kyber rack, 2027
~600 kW
Pages
6
Hub
Cooling

The heat path

Every Watt Becomes Heat That Must Leave the Building

Each Cooling page takes one step of the heat path, from chip to outdoors, with a flagship site that shows it working.

  • At the chip: air, cold plates or immersion fluid pick up the heat. Air tops out near 50 kW a rack; Nvidia's GB200 rack draws about 132 kW.
  • In the building: coolant distribution units pass heat from the rack loop to facility water.
  • Out of the building: evaporative towers use the least energy and the most water; dry coolers the reverse.
  • Water: where it comes from, aquifer, utility or recycled wastewater, matters as much as how much.

Cooling regimes

Six Pages, One Heat Path

  • Air
  • Liquid
  • Immersion
  • Heat rejection
  • Water
Cooling regimes and flagships
PageFlagshipkW per rackWater
HVAC and Air HandlingAWS Project Rainier, outside airUp to ~40-50Water a few hours a day in summer
Liquid CoolingMicrosoft Fairwater Wisconsin, closed loopFacility sideFilled once
Direct-to-ChipMicrosoft Fairwater Atlanta~140 today; ~600 by 2027None at the rack
Immersion CoolingRiot Corsicana; Sustainable Metal CloudUp to ~100 todayNone at the tank; PFAS issue for two-phase
Cooling Towers and Heat RejectionMicrosoft zero-water designn/aEvaporative to dry: 90%+ less water
Cooling Water SystemsColossus Water Recycling Plant, Memphisn/aAquifer, recycled and reclaimed water

Tradeoffs

Water, Energy and Density Trade Against Each Other

  • Water versus energy: giving up evaporation saves water but raises power use; Microsoft calls its penalty nominal. Power plants supplying data centers use about 12 times the water data centers use on site.
  • Density versus flexibility: liquid racks need facility water or sidecars; AWS and Meta built ways to run them in air-cooled halls.
  • Warm water: coolant at 45°C and above lets towers or dry coolers reject heat without chillers, and makes the heat more useful for district heating. See Heat Reuse and Resource Usage (PUE).

Record

Dataset Record

Dataset
Index of cooling regimes with flagship sites; data on each linked page
Sources
Listed on each Cooling page
Last verified
October 2026