What it is
Finding and Replacing Broken Hardware Fast
Hardware fleet management keeps tens of thousands of GPUs healthy: testing new racks, spotting failing parts, swapping them and catching chips that give wrong answers without crashing.
- Failure rates: at Meta, a 1,024-GPU job fails on average every 7.9 hours; a study at the University of Illinois found H100 memory errors 3.2 times more often than on A100.
- Silent errors: Meta now finds silent data corruption, chips returning wrong results without errors, in about 1 in 1,000 devices, and scans its whole fleet every 45-60 days.
- Spares: about 5% spare capacity is needed to keep 99.9% of jobs running, the Illinois study found.
- GB200: the first rack-scale systems shipped late after overheating, coolant leaks and NVLink backplane faults; rebuilding a rack after a backplane failure takes about nine hours or more, SemiAnalysis reports.
Flagship
Meta's Llama 3 Run: What Breaks in 54 Days
- Run: 54 days on 16,384 H100 GPUs, published by Meta in July 2024.
- Interruptions: 466 in total, 419 unexpected, about one every three hours.
- Causes: faulty GPUs 148 (30%), HBM3 memory 72 (17%), network switches and cables 35, GPU SRAM 19, GPU system processors 17, CPUs 2.
- Result: automation kept effective training time above 90%, with only three significant manual interventions. See AI Training.
Data
Failure Data and Fleet Practices
| Item | Finding | Status |
|---|---|---|
| Meta Llama 3 405B run | 419 unexpected interruptions in 54 days; GPUs and HBM cause nearly half | Measured, 2024 |
| Meta research clusters | 1,024-GPU jobs fail every 7.9 hours; finding bad nodes cut big-job failures from 14% to 4% | Measured |
| NCSA Delta study | H100 memory errors come 3.2x more often than A100; ~5% spares needed for 99.9% job availability | Measured, 2025 |
| Alibaba Unicron (China) | 1-7 failures a week on 128 GPUs; 73% transient | Measured, 2024 |
| Meta silent data corruption | ~1 in 1,000 devices; whole-fleet scans every 45-60 days | Measured, 2025 |
| GB200 rollout problems | Overheating, coolant leaks, NVLink backplane faults; firmware 1.3 fixed sync loss | Reported 2024-2025 |
| Nvidia leak handling | More than two leaking trays: building system cuts rack power and closes coolant valve | Product documentation |
| GB200 tray swap | Needs a cold rack reboot; CoreWeave drains a rack with more than two nodes down | Reported 2026 |
Record
Dataset Record
- Dataset
- GPU failure rates, silent data corruption and liquid-cooled rack servicing
- Sources
- Meta engineering and papers, NCSA (arXiv 2503.11901), Alibaba (arXiv 2401.00134), SemiAnalysis, The Information and Financial Times via DatacenterDynamics, Nvidia documentation, GMI Cloud
- Last verified
- October 2026